Ensure that all power is
switched off before
installing or maintaining
this product
Mercury 3 M & E Installation Guide
stay off.
Electric CIn – Defrost heater will go off during defrost min. period if defrost termination is achieved but will
then cycle on and off around the termination temperature setpoint until the end of the defrost min. period.
Gas (Mobile) - If gas is selected, the compressor is kept running for the duration of the defrost cycle.
Delay after the door open input is activated before the alarm occurs.
This parameter is used to close the LLV or EEV if the door opens. If the door remains open then the valve
will resume normal operation on the expiry of the door alarm delay (P-80).
This parameter is used to stop the fans if the door opens. If the door remains open then the fans will
resume normal operation on the expiry of the door alarm delay (P-80).
Allows the user to set the lights mode: -
Always off
Always on
Use a local schedule P-61 to P-74)
Use a remote schedule (Set up in the system front end)
When P-60 is set to Local, Sunday on time
When P-60 is set to Local, Sunday off time
When P-60 is set to Local, Monday on time
When P-60 is set to Local, Monday off time
When P-60 is set to Local, Tuesday on time
When P-60 is set to Local, Tuesday off time
When P-60 is set to Local, Wednesday on time
When P-60 is set to Local, Wednesday off time
When P-60 is set to Local, Thursday on time
When P-60 is set to Local, Thursday off time
When P-60 is set to Local, Friday on time
When P-60 is set to Local, Friday off time
When P-60 is set to Local, Saturday on time
When P-60 is set to Local, Saturday off time
ID of Plant Controller being used to broadcast Suction Pressure
The Broadcast ID is derived from the Rotary Switch positions set on the Plant controller which is providing
the remote suction pressure.
Note: No two Plant controllers on a local area network can have the same rotary switches positions set.
This will have adverse effects on control.
Type of refrigerant used in system. See: Refrigerant Table above
Offset to allow for pressure drop over distance
Allows the calculated temperature, derived from the Suction Pressure, to be offset by adding the value at
P-34.
Total range of the transducer
Restores all of the parameters to their default values