Mercury 3 M & E Installation Guide
Relay State and functional operation
Relay and screen states during defrost
RLY 4 Suction Line
RLY 4 Trim on in defrost
RLY 4 Trim off in defrost
Defrost Type (P-91)
If P-91 is set to gas, compressor 1 is switched on for the duration of the defrost cycle.
Defrost Termination
Defrost termination will be when the temperature parameter “def terminate” has been reached on the “defrost termination” probe. If the
“defrost termination” probe is not fitted, defrost termination will occur when: -
The “coil in” probe reaches the set point (If fans are selected as “off during defrost”)
Or The “air off” probe reaches the set point (If fans are selected as “on during defrost”)
If the “coil in” probe is not fitted, the “air off” probe will be used. If the “air off” probe is faulty termination will occur when the time-out
period has elapsed.
Fan Delay after Defrost
The fans will come back on when: -
The fan delay time has elapsed if the “fan delay mode” is set to time
Or If the fan delay mode is set to “temp”, the fans will come on when the defrost termination probe reaches the fan delay set point,
or on the time parameter, whichever occurs first.
If the “defrost termination” probe is not fitted, the fans will come on when: -
The “coil in” probe reaches the control set point (If fans are selected as “off during defrost”)
Or The “air off” probe reaches the control set point (If fans are selected as “on during defrost”)